OD MODEL | ID MODEL | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
650 | 0.98 | 0.99 |
825 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
650 | 22600 | 14.00 | 11.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 11.00 | 10.80 | 10.70 | 10.60 | 1.63 | 1.71 | 1.75 | 1.79 |
7 | 12.40 | 12.20 | 12.10 | 12.00 | 1.65 | 1.73 | 1.77 | 1.81 |
12 | 13.80 | 13.60 | 13.40 | 13.30 | 1.67 | 1.75 | 1.79 | 1.84 |
17 | 15.20 | 14.90 | 14.80 | 14.60 | 1.69 | 1.77 | 1.82 | 1.86 |
22 | 16.00 | 15.70 | 15.60 | 15.40 | 1.70 | 1.79 | 1.83 | 1.87 |
27 | 16.90 | 16.50 | 16.40 | 16.20 | 1.71 | 1.80 | 1.84 | 1.89 |
32 | 17.70 | 17.30 | 17.20 | 17.00 | 1.72 | 1.81 | 1.85 | 1.90 |
37 | 19.10 | 18.70 | 18.50 | 18.40 | 1.74 | 1.83 | 1.88 | 1.92 |
42 | 21.30 | 20.90 | 20.70 | 20.50 | 1.78 | 1.87 | 1.92 | 1.96 |
47 | 23.50 | 23.10 | 22.90 | 22.60 | 1.81 | 1.91 | 1.96 | 2.00 |
52 | 24.90 | 24.40 | 24.20 | 24.00 | 1.84 | 1.93 | 1.98 | 2.03 |
57 | 26.30 | 25.80 | 25.60 | 25.30 | 1.86 | 1.95 | 2.00 | 2.05 |
62 | 27.70 | 27.20 | 26.90 | 26.60 | 1.88 | 1.98 | 2.02 | 2.07 |
67 | 29.10 | 28.50 | 28.30 | 28.00 | 1.90 | 2.00 | 2.05 | 2.10 |
72 | 30.50 | 29.90 | 29.60 | 29.30 | 1.92 | 2.02 | 2.07 | 2.12 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
700 | 0.99 | 0.98 |
900 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
650 | 22600 | 3.60 | 14600 | 2.50 | 8.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |