OD MODEL
4TTR6048J1

ID MODEL
4PXABU48BS3

FURNACE
S9X2B080U4PSA

NOM CFM
1460

ARI REF #
10617500a

Published Date: 10/11/2021

COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES

OD AMB
ID WBTOT CAP72757880KW
85
5943.6036.0040.443.6043.603.14
6345.7029.4033.838.2041.203.17
6748.8023.0027.531.9034.803.19
7153.0017.0021.425.8028.803.22
95
5941.5035.0039.541.5041.503.52
6343.5028.4032.937.3040.203.55
6746.5022.2026.631.0034.003.59
7150.5016.1020.525.0027.903.62
105
5939.5034.1038.339.5039.503.91
6341.4027.6032.036.4039.403.94
6744.2021.3025.730.1033.103.98
7148.0015.2019.724.1027.004.02
115
5937.4033.2036.837.4037.404.29
6339.2026.7031.135.5038.504.33
6741.9020.4024.929.3032.204.37
7145.5014.4018.823.2026.204.41

USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW

AIR FLOW RATE, CFM.CAPACITY MULTIPLIERTOTAL POWER MULTIPLIER
12750.980.99
16501.021.01

ARI RATING FOR COOLING

CFMCAPACITY (A) TESTSEEREER
13004550015.0012.50

A.R.I. Standard Capacity Rating Conditions

A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.