OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1225 | 0.98 | 0.99 |
1575 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1400 | 46000 | 14.00 | 11.50 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 20.42 | 19.87 | 20.05 | 19.69 | 3.11 | 3.24 | 3.3 | 3.36 |
7 | 22.73 | 22.12 | 22.32 | 21.92 | 3.17 | 3.3 | 3.37 | 3.44 |
12 | 25.08 | 24.4 | 24.63 | 24.18 | 3.23 | 3.37 | 3.44 | 3.51 |
17 | 27.49 | 27 | 26.75 | 26.51 | 3.3 | 3.44 | 3.51 | 3.58 |
22 | 29.8 | 29.25 | 28.97 | 28.69 | 3.34 | 3.49 | 3.56 | 3.63 |
27 | 32.1 | 31.49 | 31.19 | 30.88 | 3.39 | 3.54 | 3.61 | 3.69 |
32 | 33.95 | 33.28 | 32.95 | 32.61 | 3.43 | 3.59 | 3.66 | 3.74 |
37 | 37.18 | 36.45 | 36.08 | 35.72 | 3.52 | 3.67 | 3.75 | 3.83 |
42 | 41.78 | 40.99 | 40.6 | 40.21 | 3.6 | 3.76 | 3.84 | 3.92 |
47 | 46.85 | 46 | 45.58 | 45.15 | 3.68 | 3.85 | 3.93 | 4.02 |
52 | 50.07 | 49.17 | 48.71 | 48.26 | 3.75 | 3.92 | 4 | 4.09 |
57 | 53.3 | 52.33 | 51.85 | 51.37 | 3.81 | 3.99 | 4.07 | 4.16 |
62 | 56.52 | 55.5 | 54.99 | 54.48 | 3.88 | 4.06 | 4.14 | 4.23 |
67 | 59.75 | 58.67 | 58.13 | 57.59 | 3.94 | 4.12 | 4.21 | 4.31 |
72 | 62.97 | 61.83 | 61.26 | 60.69 | 4 | 4.19 | 4.29 | 4.38 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1225 | 0.99 | 0.98 |
1575 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1225 | 45500 | 3.5 | 26800 | 2.3 | 8.2 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |