OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
COOLING PERFORMANCE AT INDOOR DRY BULB TEMPERATURES
OD AMB |
|
85 |
|
95 |
|
105 |
|
115 |
|
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1140 | 0.98 | 0.99 |
1465 | 1.02 | 1.01 |
ARI RATING FOR COOLING
CFM | CAPACITY (A) TEST | SEER | EER |
1300 | 46000 | 14.20 | 12.10 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |
OD MODEL | ID MODEL | FURNACE | NOM CFM | ARI REF # |
Published Date: 12/07/2022 |
HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE
TOTAL CAPACITY MBH. | TOTAL POWER IN KILOWATTS | |||||||
OD AMB | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
2 | 20.12 | 19.58 | 19.76 | 19.39 | 3.05 | 3.18 | 3.24 | 3.31 |
7 | 22.4 | 21.79 | 21.99 | 21.59 | 3.12 | 3.25 | 3.32 | 3.38 |
12 | 24.71 | 24.05 | 24.26 | 23.82 | 3.18 | 3.32 | 3.39 | 3.46 |
17 | 27.09 | 26.6 | 26.36 | 26.11 | 3.25 | 3.39 | 3.46 | 3.53 |
22 | 29.39 | 28.84 | 28.57 | 28.29 | 3.3 | 3.44 | 3.51 | 3.59 |
27 | 31.68 | 31.08 | 30.78 | 30.48 | 3.34 | 3.49 | 3.57 | 3.64 |
32 | 33.53 | 32.87 | 32.53 | 32.2 | 3.39 | 3.54 | 3.62 | 3.7 |
37 | 36.74 | 36.02 | 35.65 | 35.29 | 3.47 | 3.63 | 3.71 | 3.79 |
42 | 41.31 | 40.53 | 40.14 | 39.75 | 3.56 | 3.72 | 3.8 | 3.88 |
47 | 46.34 | 45.5 | 45.08 | 44.66 | 3.64 | 3.81 | 3.89 | 3.98 |
52 | 49.54 | 48.65 | 48.2 | 47.76 | 3.71 | 3.88 | 3.97 | 4.05 |
57 | 52.75 | 51.8 | 51.32 | 50.85 | 3.78 | 3.95 | 4.04 | 4.12 |
62 | 55.96 | 54.95 | 54.44 | 53.94 | 3.84 | 4.02 | 4.11 | 4.2 |
67 | 59.17 | 58.1 | 57.57 | 57.03 | 3.91 | 4.09 | 4.18 | 4.27 |
72 | 62.38 | 61.25 | 60.69 | 60.12 | 3.97 | 4.16 | 4.25 | 4.35 |
USE THE FOLLOWING FACTORS TO COMPENSATE FOR DIFFERENT AIR FLOW
AIR FLOW RATE, CFM. | CAPACITY MULTIPLIER | TOTAL POWER MULTIPLIER |
1140 | 0.99 | 0.98 |
1465 | 1.01 | 1.03 |
ARI RATING FOR HEATING
CFM | CAPACITY 47 | COP 47 | CAPACITY 17 | COP 17 | HSPF |
1140 | 45000 | 3.5 | 26400 | 2.3 | 8.2 |
A.R.I. Standard Capacity Rating Conditions |
A.R.I. STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F. D.B., 67°F. W.B. air entering indoor coil, 95°F. D.B. air entering outdoor coil. (B) High Temperature Heating 47°F. D.B., 43°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (C) Low Temperature Heating 17°F. D.B. ,15°F. W.B. air entering outdoor coil, 70°F. D.B. air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling. |